SAMPLE — fictional system, for illustration only
Sample 1 — Functional Design Specification (excerpt)
Fictional system: “Line 1 Bottle Filler — Transfer Pump P-101”
- Purpose: Transfer product from Tank T-100 to the filler bowl on demand.
- Operating modes: Auto · Manual (HMI) · Off.
- Start permissives: T-100 level > 10 % · discharge valve XV-102 proven open · no active P-101 fault.
- Run logic (Auto): start when filler bowl level < 40 %; stop at 80 %.
- Interlocks: stop P-101 if XV-102 open feedback is lost for > 3 s; stop on T-100 low-low level.
- Alarms: P-101 fail to start (5 s) · XV-102 position mismatch · T-100 low-low level.
SAMPLE — fictional system, for illustration only
Sample 2 — FAT checklist (excerpt)
| Step | Test | Expected result | Pass/Fail | Initials |
|---|---|---|---|---|
| 1 | Start P-101 in Auto with all permissives met | Pump runs; HMI shows Running | ||
| 2 | Close XV-102 while P-101 runs | P-101 stops within 3 s; alarm "XV-102 position mismatch" | ||
| 3 | Simulate T-100 low-low | P-101 stops; alarm raised; restart blocked until reset |
SAMPLE — fictional system, for illustration only
Sample 3 — EPLAN drawing excerpt