Analog signal scaling

Convert a 4–20 mA or 0–10 V field signal to engineering units and percent of span.

Inputs

Calculations run in your browser. Your input values are not submitted or saved.

Results

Engineering value
50
Percent of span
50 %

Linear two-point scaling only. It does not linearize nonlinear sensors (RTD, thermocouple, square-root flow) and does not replace a documented loop calibration.

Formula & guidance

EU = EU_low + (reading − sig_low) ÷ (sig_high − sig_low) × (EU_high − EU_low)

Linear two-point scaling only. It does not linearize nonlinear sensors (RTD, thermocouple, square-root flow) and does not replace a documented loop calibration.

Change the example inputs and check each field’s units. Use equipment datasheets and applicable project standards for final decisions. Results do not establish Canadian electrical-code compliance or certify a design.